BC/BD-2X150BD5-B09 C
43.25 kW
Defrost: None
Product code: BC/BD-t-263AA5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 18,056 m³/h |
|---|---|
| External surface | 78.8 m² |
| Inner volume | 12.4 dm³ |
| Fin material | Aluminium |
| Net weight | 195 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 77.6 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-t-263AA5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 24.27 | not rated | not rated | not rated | not rated | not rated |
| 40 | 43.25 | 24.46 | not rated | not rated | not rated | not rated |
| 45 | 61.84 | 43.33 | 24.62 | not rated | not rated | not rated |
| 50 | 80.31 | 61.83 | 43.40 | 24.76 | not rated | not rated |
| 55 | 98.72 | 80.21 | 61.83 | 43.47 | 24.89 | not rated |
| 60 | 117.10 | 98.55 | 80.14 | 61.84 | 43.56 | 25.03 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 43.249 | 7.51 | 43.1 |
| A | 2150 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 2400 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2150 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.