BC/BD-363CA1-B01 C
63.60 kW
Defrost: None
Product code: BC/BD-t-280GC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 14,293 m³/h |
|---|---|
| External surface | 217.1 m² |
| Inner volume | 24.1 dm³ |
| Fin material | Aluminium |
| Net weight | 322 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-t-280GC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 39.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 63.53 | 39.16 | not rated | not rated | not rated | not rated |
| 45 | 87.15 | 63.42 | 39.22 | not rated | not rated | not rated |
| 50 | 110.52 | 86.91 | 63.36 | 39.32 | not rated | not rated |
| 55 | 133.77 | 110.16 | 86.76 | 63.39 | 39.46 | not rated |
| 60 | 156.95 | 133.29 | 109.92 | 86.73 | 63.51 | 39.67 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | 28.79 | not rated | not rated | not rated |
| 50 | not rated | not rated | 45.91 | 28.89 | not rated | not rated |
| 55 | not rated | not rated | 62.48 | 45.98 | 29.02 | not rated |
| 60 | not rated | not rated | 78.89 | 62.54 | 46.10 | 29.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 63.529 | 11.02 | 89.0 |
| Low speed (Y) | — | — | — |
| A | 2450 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2200 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 2750 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2750 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.