Skip to Content

Dry cooler BC/BD-t-280LB1-B03 C

Dry cooler BC/BD-t-280LB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-280LB1-B03 C

Heat rejection i
90.53 kW
Air flow
20,738 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 20,738 m³/h
External surface 372.2 m²
Inner volume 41.0 dm³
Fin materialAluminium
Net weight 458 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class B
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-t-280LB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
90.528 kW Fluid flow 15.70 m³/h Pressure drop 83.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
70.522 kW Fluid flow 12.23 m³/h Pressure drop 53.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 55.69 not rated not rated not rated not rated not rated
40 90.53 55.52 not rated not rated not rated not rated
45 124.31 90.00 55.38 not rated not rated not rated
50 157.74 123.45 89.54 55.27 not rated not rated
55 191.02 156.57 122.71 89.18 55.22 not rated
60 224.21 189.54 155.57 122.13 88.95 55.25

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 43.79 not rated not rated not rated not rated not rated
40 70.52 43.66 not rated not rated not rated not rated
45 96.40 70.10 43.54 not rated not rated not rated
50 122.01 95.73 69.74 43.46 not rated not rated
55 147.50 121.10 95.16 69.47 43.42 not rated
60 172.91 146.36 120.33 94.72 69.29 43.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 90.528 15.70 83.7
Low speed (Y) 70.522 12.23 53.7

Dimensions

Dimension drawing of BC/BD-t-280LB1-B03 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 1180 mm
K 5450 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 5450 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.