BC/BD-380HA1-B01 C
92.88 kW
Defrost: None
Product code: BC/BD-t-280LC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 20,319 m³/h |
|---|---|
| External surface | 420.4 m² |
| Inner volume | 52.8 dm³ |
| Fin material | Aluminium |
| Net weight | 482 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-280LC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 57.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.92 | 57.65 | not rated | not rated | not rated | not rated |
| 45 | 126.83 | 92.29 | 57.46 | not rated | not rated | not rated |
| 50 | 160.39 | 125.85 | 91.75 | 57.31 | not rated | not rated |
| 55 | 193.79 | 159.08 | 125.02 | 91.33 | 57.23 | not rated |
| 60 | 227.10 | 192.15 | 157.96 | 124.35 | 91.05 | 57.24 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 44.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 71.03 | 44.52 | not rated | not rated | not rated | not rated |
| 45 | 96.51 | 70.59 | 44.40 | not rated | not rated | not rated |
| 50 | 121.74 | 95.83 | 70.22 | 44.31 | not rated | not rated |
| 55 | 146.84 | 120.83 | 95.26 | 69.95 | 44.28 | not rated |
| 60 | 171.89 | 145.71 | 120.06 | 94.83 | 69.79 | 44.33 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 92.917 | 16.12 | 56.2 |
| Low speed (Y) | 71.026 | 12.32 | 34.8 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 5450 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 5450 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.