BC/BD-291GB5-B04 C
142.79 kW
Defrost: None
Product code: BC/BD-t-291OC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,275 m³/h |
|---|---|
| External surface | 245.2 m² |
| Inner volume | 37.4 dm³ |
| Fin material | Aluminium |
| Net weight | 378 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 94.9 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-291OC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 82.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 142.80 | 82.86 | not rated | not rated | not rated | not rated |
| 45 | 201.69 | 142.92 | 83.27 | not rated | not rated | not rated |
| 50 | 260.09 | 201.51 | 143.06 | 83.68 | not rated | not rated |
| 55 | 318.26 | 259.65 | 201.43 | 143.27 | 84.10 | not rated |
| 60 | 376.30 | 317.55 | 259.33 | 201.47 | 143.58 | 84.57 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 142.802 | 24.79 | 67.4 |
| A | 3150 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2900 mm |
| H | 1400 mm |
| I | 1180 mm |
| K | 3450 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3450 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.