BC/BD-t-663AD1-B01 C
205.85 kW
Defrost: None
Product code: BC/BD-t-291RC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 52,096 m³/h |
|---|---|
| External surface | 496.3 m² |
| Inner volume | 60.4 dm³ |
| Fin material | Aluminium |
| Net weight | 510 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.5 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-291RC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 122.36 | not rated | not rated | not rated | not rated | not rated |
| 40 | 205.71 | 122.52 | not rated | not rated | not rated | not rated |
| 45 | 286.52 | 205.11 | 122.66 | not rated | not rated | not rated |
| 50 | 366.46 | 285.25 | 204.60 | 122.79 | not rated | not rated |
| 55 | 446.00 | 364.56 | 284.18 | 204.26 | 123.03 | not rated |
| 60 | 525.31 | 443.49 | 362.96 | 283.40 | 204.14 | 123.39 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 94.90 | not rated | not rated | not rated | not rated | not rated |
| 40 | 157.69 | 95.01 | not rated | not rated | not rated | not rated |
| 45 | 218.34 | 157.21 | 95.12 | not rated | not rated | not rated |
| 50 | 278.26 | 217.33 | 156.81 | 95.25 | not rated | not rated |
| 55 | 337.85 | 276.78 | 216.52 | 156.56 | 95.46 | not rated |
| 60 | 397.26 | 335.91 | 275.57 | 215.94 | 156.50 | 95.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 205.707 | 35.68 | 69.4 |
| Low speed (Y) | 157.693 | 27.34 | 43.2 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 5450 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5450 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.