BC/BD-350CC1-B09 C
57.36 kW
Defrost: None
Product code: BC/BD-t-2X163AA1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 23,817 m³/h |
|---|---|
| External surface | 91.9 m² |
| Inner volume | 15.4 dm³ |
| Fin material | Aluminium |
| Net weight | 192 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-t-2X163AA1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 32.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 57.37 | 32.42 | not rated | not rated | not rated | not rated |
| 45 | 82.06 | 57.45 | 32.62 | not rated | not rated | not rated |
| 50 | 106.59 | 82.01 | 57.52 | 32.79 | not rated | not rated |
| 55 | 131.06 | 106.42 | 81.98 | 57.60 | 32.95 | not rated |
| 60 | 155.48 | 130.77 | 106.29 | 81.97 | 57.69 | 33.11 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 49.62 | 28.19 | not rated | not rated | not rated | not rated |
| 45 | 70.78 | 49.68 | 28.35 | not rated | not rated | not rated |
| 50 | 91.80 | 70.73 | 49.73 | 28.50 | not rated | not rated |
| 55 | 112.75 | 91.64 | 70.69 | 49.80 | 28.65 | not rated |
| 60 | 133.66 | 112.49 | 91.51 | 70.68 | 49.89 | 28.80 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 57.370 | 9.96 | 83.0 |
| Low speed (Y) | 49.619 | 8.61 | 64.2 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 1500 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1250 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.