BC/BD-363CB5-B01 C
72.45 kW
Defrost: None
Product code: BC/BD-t-2X163AB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,678 m³/h |
|---|---|
| External surface | 137.8 m² |
| Inner volume | 23.7 dm³ |
| Fin material | Aluminium |
| Net weight | 206 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-2X163AB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 41.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 72.52 | 41.70 | not rated | not rated | not rated | not rated |
| 45 | 102.76 | 72.52 | 41.91 | not rated | not rated | not rated |
| 50 | 132.74 | 102.56 | 72.53 | 42.09 | not rated | not rated |
| 55 | 162.59 | 132.35 | 102.41 | 72.56 | 42.28 | not rated |
| 60 | 192.38 | 162.02 | 132.04 | 102.31 | 72.65 | 42.49 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 35.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 61.10 | 35.38 | not rated | not rated | not rated | not rated |
| 45 | 86.25 | 61.08 | 35.55 | not rated | not rated | not rated |
| 50 | 111.16 | 86.06 | 61.07 | 35.71 | not rated | not rated |
| 55 | 135.95 | 110.80 | 85.89 | 61.09 | 35.86 | not rated |
| 60 | 160.68 | 135.43 | 110.50 | 85.80 | 61.15 | 36.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 72.518 | 12.59 | 59.3 |
| Low speed (Y) | 61.100 | 10.61 | 43.7 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 1500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1250 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.