BC/BD-380AB5-B03 C
82.84 kW
Defrost: None
Product code: BC/BD-t-2X163AC1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 21,658 m³/h |
|---|---|
| External surface | 183.7 m² |
| Inner volume | 28.1 dm³ |
| Fin material | Aluminium |
| Net weight | 219 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-2X163AC1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 48.70 | not rated | not rated | not rated | not rated | not rated |
| 40 | 82.84 | 48.86 | not rated | not rated | not rated | not rated |
| 45 | 115.92 | 82.70 | 48.99 | not rated | not rated | not rated |
| 50 | 148.65 | 115.53 | 82.59 | 49.13 | not rated | not rated |
| 55 | 181.20 | 148.01 | 115.20 | 82.53 | 49.29 | not rated |
| 60 | 213.66 | 180.33 | 147.49 | 114.98 | 82.56 | 49.49 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 40.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 67.92 | 40.46 | not rated | not rated | not rated | not rated |
| 45 | 94.60 | 67.85 | 40.59 | not rated | not rated | not rated |
| 50 | 120.96 | 94.35 | 67.82 | 40.72 | not rated | not rated |
| 55 | 147.17 | 120.55 | 94.17 | 67.80 | 40.86 | not rated |
| 60 | 173.30 | 146.60 | 120.23 | 94.03 | 67.82 | 41.03 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 82.837 | 14.37 | 64.1 |
| Low speed (Y) | 67.916 | 11.78 | 45.0 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 1500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1250 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.