BC/BD-t-350AB1-B09 C
68.34 kW
Defrost: None
Product code: BC/BD-t-2X163AD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 14,833 m³/h |
|---|---|
| External surface | 229.6 m² |
| Inner volume | 40.2 dm³ |
| Fin material | Aluminium |
| Net weight | 233 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 78.1 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-2X163AD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 42.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 68.25 | 42.26 | not rated | not rated | not rated | not rated |
| 45 | 93.28 | 67.96 | 42.24 | not rated | not rated | not rated |
| 50 | 118.00 | 92.78 | 67.74 | 42.25 | not rated | not rated |
| 55 | 142.59 | 117.31 | 92.39 | 67.60 | 42.32 | not rated |
| 60 | 167.11 | 141.71 | 116.76 | 92.12 | 67.57 | 42.45 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 68.251 | 11.84 | 61.5 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 1500 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 1250 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.