BC/BD-t-280JC1-B03 C
85.42 kW
Defrost: None
Product code: BC/BD-t-2X163AD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 21,212 m³/h |
|---|---|
| External surface | 194.5 m² |
| Inner volume | 40.2 dm³ |
| Fin material | Aluminium |
| Net weight | 228 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-2X163AD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 51.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 85.38 | 51.30 | not rated | not rated | not rated | not rated |
| 45 | 118.47 | 85.11 | 51.32 | not rated | not rated | not rated |
| 50 | 151.23 | 117.95 | 84.90 | 51.36 | not rated | not rated |
| 55 | 183.82 | 150.46 | 117.52 | 84.75 | 51.45 | not rated |
| 60 | 216.33 | 182.82 | 149.82 | 117.21 | 84.71 | 51.60 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 41.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 68.65 | 41.73 | not rated | not rated | not rated | not rated |
| 45 | 94.80 | 68.58 | 41.82 | not rated | not rated | not rated |
| 50 | 120.66 | 94.59 | 68.52 | 41.93 | not rated | not rated |
| 55 | 146.39 | 120.32 | 94.41 | 68.53 | 42.07 | not rated |
| 60 | 172.04 | 145.92 | 120.03 | 94.33 | 68.62 | 42.27 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 85.379 | 14.81 | 91.2 |
| Low speed (Y) | 68.648 | 11.90 | 62.1 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 1500 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 1250 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.