BC/BD-t-2X263AA5-B01 C
85.95 kW
Defrost: None
Product code: BC/BD-t-2X180GB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 32,565 m³/h |
|---|---|
| External surface | 136.2 m² |
| Inner volume | 33.6 dm³ |
| Fin material | Aluminium |
| Net weight | 308 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 84.6 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-2X180GB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 48.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 85.97 | 48.50 | not rated | not rated | not rated | not rated |
| 45 | 123.08 | 86.29 | 48.94 | not rated | not rated | not rated |
| 50 | 159.92 | 123.27 | 86.60 | 49.35 | not rated | not rated |
| 55 | 196.63 | 159.99 | 123.47 | 86.92 | 49.75 | not rated |
| 60 | 233.28 | 196.58 | 160.10 | 123.74 | 87.28 | 50.15 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 38.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 69.00 | 39.24 | not rated | not rated | not rated | not rated |
| 45 | 98.35 | 69.25 | 39.61 | not rated | not rated | not rated |
| 50 | 127.45 | 98.48 | 69.48 | 39.94 | not rated | not rated |
| 55 | 156.42 | 127.47 | 98.63 | 69.74 | 40.27 | not rated |
| 60 | 185.33 | 156.34 | 127.55 | 98.84 | 70.04 | 40.61 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 85.973 | 14.92 | 38.8 |
| Low speed (Y) | 69.004 | 11.98 | 26.3 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 1700 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 1400 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.