BC/BD-t-463AC1-B01 C
132.19 kW
Defrost: None
Product code: BC/BD-t-2X263AB5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 46,039 m³/h |
|---|---|
| External surface | 233.4 m² |
| Inner volume | 50.9 dm³ |
| Fin material | Aluminium |
| Net weight | 343 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2X263AB5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 74.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 132.19 | 75.41 | not rated | not rated | not rated | not rated |
| 45 | 188.09 | 132.29 | 75.84 | not rated | not rated | not rated |
| 50 | 243.56 | 187.87 | 132.40 | 76.22 | not rated | not rated |
| 55 | 298.84 | 243.04 | 187.70 | 132.53 | 76.60 | not rated |
| 60 | 354.00 | 298.01 | 242.60 | 187.61 | 132.72 | 76.99 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 64.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 112.45 | 64.54 | not rated | not rated | not rated | not rated |
| 45 | 159.50 | 112.50 | 64.89 | not rated | not rated | not rated |
| 50 | 206.13 | 159.26 | 112.57 | 65.22 | not rated | not rated |
| 55 | 252.58 | 205.62 | 159.07 | 112.66 | 65.54 | not rated |
| 60 | 298.92 | 251.80 | 205.20 | 158.97 | 112.82 | 65.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 132.187 | 22.94 | 42.4 |
| Low speed (Y) | 112.449 | 19.52 | 31.9 |
| A | 2150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 2400 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 2150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.