Skip to Content

Dry cooler BC/BD-t-2X263AC1-B19 C

Dry cooler BC/BD-t-2X263AC1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X263AC1-B19 C

Heat rejection i
168.40 kW
Air flow
43,316 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,316 m³/h
External surface 367.4 m²
Inner volume 59.7 dm³
Fin materialAluminium
Net weight 374 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2X263AC1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
168.397 kW Fluid flow 29.20 m³/h Pressure drop 116.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
137.899 kW Fluid flow 23.91 m³/h Pressure drop 82.1 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 100.47 not rated not rated not rated not rated not rated
40 168.40 100.57 not rated not rated not rated not rated
45 234.42 167.96 100.67 not rated not rated not rated
50 299.79 233.49 167.60 100.79 not rated not rated
55 364.86 298.40 232.73 167.38 100.96 not rated
60 429.75 363.01 297.25 232.20 167.34 101.27

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 83.00 not rated not rated not rated not rated not rated
40 137.90 83.16 not rated not rated not rated not rated
45 191.10 137.65 83.30 not rated not rated not rated
50 243.74 190.51 137.47 83.43 not rated not rated
55 296.12 242.83 190.06 137.34 83.60 not rated
60 348.34 294.90 242.12 189.70 137.31 83.86

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 168.397 29.20 116.8
Low speed (Y) 137.899 23.91 82.1

Dimensions

Dimension drawing of BC/BD-t-2X263AC1-B19 C
Dimension drawing
Dimensions as drawn
A 2150 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 1900 mm
H 900 mm
I 2260 mm
K 2400 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 2150 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.