Skip to Content

Dry cooler BC/BD-t-2X280GB5-B01 C

Dry cooler BC/BD-t-2X280GB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X280GB5-B01 C

Heat rejection i
171.65 kW
Air flow
65,129 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 65,129 m³/h
External surface 272.3 m²
Inner volume 55.3 dm³
Fin materialAluminium
Net weight 544 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 87.6 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2X280GB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
171.650 kW Fluid flow 29.79 m³/h Pressure drop 37.3 kPa
Heat rejection · Low speed (Y)
137.784 kW Fluid flow 23.92 m³/h Pressure drop 25.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 95.69 not rated not rated not rated not rated not rated
40 171.65 96.71 not rated not rated not rated not rated
45 245.87 172.30 97.61 not rated not rated not rated
50 319.56 246.26 172.93 98.44 not rated not rated
55 392.99 319.70 246.68 173.59 99.24 not rated
60 466.28 392.90 319.94 247.21 174.30 100.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 77.44 not rated not rated not rated not rated not rated
40 137.78 78.26 not rated not rated not rated not rated
45 196.49 138.28 79.00 not rated not rated not rated
50 254.68 196.75 138.77 79.68 not rated not rated
55 312.63 254.73 197.06 139.29 80.35 not rated
60 370.45 312.49 254.90 197.49 139.88 81.03

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 171.650 29.79 37.3
Low speed (Y) 137.784 23.92 25.2

Dimensions

Dimension drawing of BC/BD-t-2X280GB5-B01 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 2260 mm
K 2750 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 2450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.