BC/BD-2X463BD5-B01 C
226.60 kW
Defrost: None
Product code: BC/BD-t-2X380GA1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 105,445 m³/h |
|---|---|
| External surface | 321.5 m² |
| Inner volume | 55.3 dm³ |
| Fin material | Aluminium |
| Net weight | 744 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2X380GA1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 124.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 226.76 | 126.26 | not rated | not rated | not rated | not rated |
| 45 | 326.77 | 227.69 | 127.46 | not rated | not rated | not rated |
| 50 | 426.23 | 327.37 | 228.57 | 128.53 | not rated | not rated |
| 55 | 525.42 | 426.53 | 327.99 | 229.43 | 129.55 | not rated |
| 60 | 624.47 | 525.44 | 426.92 | 328.68 | 230.33 | 130.55 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 103.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 185.86 | 104.20 | not rated | not rated | not rated | not rated |
| 45 | 266.85 | 186.53 | 105.14 | not rated | not rated | not rated |
| 50 | 347.29 | 267.20 | 187.16 | 106.01 | not rated | not rated |
| 55 | 427.49 | 347.35 | 267.58 | 187.80 | 106.83 | not rated |
| 60 | 507.54 | 427.28 | 347.51 | 268.04 | 188.49 | 107.65 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 226.759 | 39.36 | 59.1 |
| Low speed (Y) | 185.856 | 32.25 | 41.4 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3500 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.