Skip to Content

Dry cooler BC/BD-t-2X463AA1-B19 C

Dry cooler BC/BD-t-2X463AA1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X463AA1-B19 C

Heat rejection i
228.83 kW
Air flow
95,267 m³/h
Fans
8 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 95,267 m³/h
External surface 367.4 m²
Inner volume 59.7 dm³
Fin materialAluminium
Net weight 583 kg
Fans
Quantity 8
Diameter 630 mm
Speed 1,330 rpm
Power 10,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2X463AA1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
228.831 kW Fluid flow 39.71 m³/h Pressure drop 66.9 kPa
Heat rejection · Low speed (Y)
197.933 kW Fluid flow 34.35 m³/h Pressure drop 51.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 128.15 not rated not rated not rated not rated not rated
40 228.83 129.07 not rated not rated not rated not rated
45 327.60 229.19 129.88 not rated not rated not rated
50 425.73 327.44 229.50 130.58 not rated not rated
55 523.60 425.09 327.32 229.83 131.26 not rated
60 621.30 522.50 424.57 327.30 230.22 131.93

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 111.43 not rated not rated not rated not rated not rated
40 197.93 112.22 not rated not rated not rated not rated
45 282.59 198.20 112.90 not rated not rated not rated
50 366.68 282.41 198.44 113.52 not rated not rated
55 450.48 366.06 282.27 198.72 114.12 not rated
60 534.13 449.45 365.57 282.26 199.09 114.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 228.831 39.71 66.9
Low speed (Y) 197.933 34.35 51.7

Dimensions

Dimension drawing of BC/BD-t-2X463AA1-B19 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 2260 mm
K 4200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3950 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.