Skip to Content

Dry cooler BC/BD-t-2X463AC1-B19 C

Dry cooler BC/BD-t-2X463AC1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X463AC1-B19 C

Heat rejection i
336.57 kW
Air flow
86,632 m³/h
Fans
8 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 86,632 m³/h
External surface 734.8 m²
Inner volume 112.0 dm³
Fin materialAluminium
Net weight 685 kg
Fans
Quantity 8
Diameter 630 mm
Speed 1,330 rpm
Power 10,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X463AC1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
336.567 kW Fluid flow 58.37 m³/h Pressure drop 110.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
275.628 kW Fluid flow 47.80 m³/h Pressure drop 77.2 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 200.69 not rated not rated not rated not rated not rated
40 336.57 200.91 not rated not rated not rated not rated
45 468.63 335.70 201.10 not rated not rated not rated
50 599.37 466.78 335.00 201.38 not rated not rated
55 729.50 596.60 465.27 334.56 201.73 not rated
60 859.29 725.82 594.31 464.20 334.49 202.34

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 165.81 not rated not rated not rated not rated not rated
40 275.63 166.12 not rated not rated not rated not rated
45 382.05 275.14 166.43 not rated not rated not rated
50 487.33 380.88 274.79 166.70 not rated not rated
55 592.08 485.52 379.98 274.54 167.04 not rated
60 696.53 589.65 484.10 379.25 274.48 167.56

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 336.567 58.37 110.0
Low speed (Y) 275.628 47.80 77.2

Dimensions

Dimension drawing of BC/BD-t-2X463AC1-B19 C
Dimension drawing
Dimensions as drawn
A 4050 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 2260 mm
K 4400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4050 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.