BC/BD-880AD5-B01 C
416.10 kW
Defrost: None
Product code: BC/BD-t-2X563AC1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 108,289 m³/h |
|---|---|
| External surface | 918.5 m² |
| Inner volume | 129.6 dm³ |
| Fin material | Aluminium |
| Net weight | 841 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 12,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2X563AC1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 245.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 416.14 | 246.35 | not rated | not rated | not rated | not rated |
| 45 | 581.44 | 415.30 | 246.89 | not rated | not rated | not rated |
| 50 | 745.00 | 579.36 | 414.67 | 247.47 | not rated | not rated |
| 55 | 907.73 | 741.73 | 577.66 | 414.31 | 248.18 | not rated |
| 60 | 1070.00 | 903.32 | 739.04 | 576.49 | 414.37 | 249.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 203.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 341.07 | 203.94 | not rated | not rated | not rated | not rated |
| 45 | 474.35 | 340.66 | 204.50 | not rated | not rated | not rated |
| 50 | 606.09 | 473.06 | 340.41 | 205.06 | not rated | not rated |
| 55 | 737.12 | 603.98 | 472.08 | 340.24 | 205.63 | not rated |
| 60 | 867.74 | 734.21 | 602.34 | 471.30 | 340.29 | 206.44 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 416.135 | 72.17 | 70.1 |
| Low speed (Y) | 341.069 | 59.15 | 49.1 |
| A | 4950 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 5300 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4950 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.