Dry cooler BC/BD-t-2X580GB5-B01 C

Dry cooler BC/BD-t-2X580GB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X580GB5-B01 C

Heat rejection i
420.03 kW
Air flow
162,823 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 162,823 m³/h
External surface 680.8 m²
Inner volume 140.4 dm³
Fin materialAluminium
Net weight 1,255 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.6 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X580GB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
420.026 kW Fluid flow 72.89 m³/h Pressure drop 21.2 kPa
Heat rejection · Low speed (Y)
337.448 kW Fluid flow 58.56 m³/h Pressure drop 14.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 229.28 not rated not rated not rated not rated not rated
40 420.03 232.57 not rated not rated not rated not rated
45 605.93 422.20 235.41 not rated not rated not rated
50 790.35 607.31 424.20 237.98 not rated not rated
55 974.08 791.06 608.73 426.19 240.42 not rated
60 1157.42 974.18 791.99 610.36 428.30 242.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 185.58 not rated not rated not rated not rated not rated
40 337.45 188.32 not rated not rated not rated not rated
45 484.60 339.12 190.67 not rated not rated not rated
50 630.31 485.59 340.69 192.78 not rated not rated
55 775.34 630.73 486.66 342.29 194.82 not rated
60 920.01 775.24 631.38 487.95 344.03 196.83

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 420.026 72.89 21.2
Low speed (Y) 337.448 58.56 14.3

Dimensions

Dimension drawing of BC/BD-t-2X580GB5-B01 C
Dimension drawing
Dimensions as drawn
A 5800 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1050 mm
I 2260 mm
K 6300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 5800 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.