Skip to Content

Dry cooler BC/BD-t-2X663AA5-B19 C

Dry cooler BC/BD-t-2X663AA5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X663AA5-B19 C

Heat rejection i
297.34 kW
Air flow
144,341 m³/h
Fans
12 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 144,341 m³/h
External surface 466.9 m²
Inner volume 94.4 dm³
Fin materialAluminium
Net weight 834 kg
Fans
Quantity 12
Diameter 630 mm
Speed 1,330 rpm
Power 15,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X663AA5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
297.342 kW Fluid flow 51.60 m³/h Pressure drop 24.6 kPa
Heat rejection · Low speed (Y)
259.326 kW Fluid flow 45.01 m³/h Pressure drop 19.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 161.15 not rated not rated not rated not rated not rated
40 297.34 163.18 not rated not rated not rated not rated
45 430.74 298.49 164.89 not rated not rated not rated
50 563.31 431.18 299.47 166.38 not rated not rated
55 695.51 563.13 431.59 300.38 167.74 not rated
60 827.50 694.74 563.01 432.04 301.30 169.01

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 141.09 not rated not rated not rated not rated not rated
40 259.33 142.89 not rated not rated not rated not rated
45 374.77 260.29 144.42 not rated not rated not rated
50 489.41 375.12 261.14 145.77 not rated not rated
55 603.68 489.22 375.47 261.95 146.99 not rated
60 717.77 602.97 489.10 375.89 262.79 148.14

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 297.342 51.60 24.6
Low speed (Y) 259.326 45.01 19.2

Dimensions

Dimension drawing of BC/BD-t-2X663AA5-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 2260 mm
K 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.