Skip to Content

Dry cooler BC/BD-t-2X663AB5-B19 C

Dry cooler BC/BD-t-2X663AB5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X663AB5-B19 C

Heat rejection i
384.70 kW
Air flow
138,118 m³/h
Fans
12 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 138,118 m³/h
External surface 700.3 m²
Inner volume 142.6 dm³
Fin materialAluminium
Net weight 907 kg
Fans
Quantity 12
Diameter 630 mm
Speed 1,330 rpm
Power 15,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X663AB5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
384.695 kW Fluid flow 66.77 m³/h Pressure drop 18.5 kPa
Heat rejection · Low speed (Y)
327.591 kW Fluid flow 56.86 m³/h Pressure drop 13.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 211.69 not rated not rated not rated not rated not rated
40 384.70 214.16 not rated not rated not rated not rated
45 552.85 385.71 216.27 not rated not rated not rated
50 719.54 552.79 386.61 218.11 not rated not rated
55 885.55 718.45 552.77 387.53 219.80 not rated
60 1051.15 883.52 717.62 552.94 388.54 221.48

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 181.23 not rated not rated not rated not rated not rated
40 327.59 183.37 not rated not rated not rated not rated
45 469.22 328.35 185.17 not rated not rated not rated
50 609.41 468.99 329.04 186.77 not rated not rated
55 748.95 608.29 468.87 329.75 188.24 not rated
60 888.10 746.98 607.42 468.93 330.62 189.69

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 384.695 66.77 18.5
Low speed (Y) 327.591 56.86 13.9

Dimensions

Dimension drawing of BC/BD-t-2X663AB5-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 2260 mm
K 6200 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 5850 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.