BC/BD-2x680AD1-B03 C
393.84 kW
Defrost: None
Product code: BC/BD-t-2X663AD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 91,460 m³/h |
|---|---|
| External surface | 1,167.1 m² |
| Inner volume | 195.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,047 kg |
| Quantity | 12 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 7,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 85.8 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-t-2X663AD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 239.81 | not rated | not rated | not rated | not rated | not rated |
| 40 | 394.44 | 239.96 | not rated | not rated | not rated | not rated |
| 45 | 543.87 | 393.23 | 240.15 | not rated | not rated | not rated |
| 50 | 691.58 | 541.50 | 392.30 | 240.46 | not rated | not rated |
| 55 | 838.50 | 688.14 | 539.64 | 391.78 | 241.01 | not rated |
| 60 | 984.98 | 834.01 | 685.40 | 538.43 | 391.80 | 241.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 394.444 | 68.42 | 47.8 |
| A | 5850 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 5500 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 6200 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 5850 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.