BC/BD-263CD5-B01 C
58.93 kW
Defrost: None
Product code: BC/BD-t-2x180GB1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 15,684 m³/h |
|---|---|
| External surface | 160.7 m² |
| Inner volume | 22.0 dm³ |
| Fin material | Aluminium |
| Net weight | 303 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-t-2x180GB1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 34.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 59.00 | 34.86 | not rated | not rated | not rated | not rated |
| 45 | 82.57 | 59.01 | 35.02 | not rated | not rated | not rated |
| 50 | 105.90 | 82.46 | 59.05 | 35.19 | not rated | not rated |
| 55 | 129.11 | 105.66 | 82.39 | 59.13 | 35.37 | not rated |
| 60 | 152.25 | 128.76 | 105.51 | 82.41 | 59.27 | 35.58 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 26.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 44.89 | 26.84 | not rated | not rated | not rated | not rated |
| 45 | 62.46 | 44.93 | 26.99 | not rated | not rated | not rated |
| 50 | 79.83 | 62.43 | 45.01 | 27.15 | not rated | not rated |
| 55 | 97.10 | 79.73 | 62.45 | 45.12 | 27.32 | not rated |
| 60 | 114.31 | 96.93 | 79.69 | 62.53 | 45.28 | 27.53 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 58.995 | 10.23 | 53.7 |
| Low speed (Y) | 44.885 | 7.78 | 32.9 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 1700 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1700 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.