Skip to Content

Dry cooler BC/BD-t-2x180JC5-B01 C

Dry cooler BC/BD-t-2x180JC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x180JC5-B01 C

Heat rejection i
137.47 kW
Air flow
37,413 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 37,413 m³/h
External surface 302.6 m²
Inner volume 52.4 dm³
Fin materialAluminium
Net weight 398 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 52.0 dB(A)
Sound power 83.4 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2x180JC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
137.467 kW Fluid flow 23.86 m³/h Pressure drop 83.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
106.117 kW Fluid flow 18.40 m³/h Pressure drop 52.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 81.37 not rated not rated not rated not rated not rated
40 137.47 81.55 not rated not rated not rated not rated
45 192.03 137.25 81.73 not rated not rated not rated
50 246.10 191.49 137.10 81.92 not rated not rated
55 299.94 245.24 191.06 137.06 82.16 not rated
60 353.65 298.76 244.55 190.81 137.14 82.47

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 63.50 not rated not rated not rated not rated not rated
40 106.12 63.60 not rated not rated not rated not rated
45 147.45 105.86 63.69 not rated not rated not rated
50 188.37 146.90 105.67 63.78 not rated not rated
55 229.08 187.53 146.46 105.56 63.94 not rated
60 269.68 227.97 186.86 146.16 105.57 64.15

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 137.467 23.86 83.1
Low speed (Y) 106.117 18.40 52.4

Dimensions

Dimension drawing of BC/BD-t-2x180JC5-B01 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 2260 mm
K 2400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.