Skip to Content

Dry cooler BC/BD-t-2x180LB5-B01 C

Dry cooler BC/BD-t-2x180LB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x180LB5-B01 C

Heat rejection i
139.37 kW
Air flow
42,082 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 42,082 m³/h
External surface 311.2 m²
Inner volume 53.4 dm³
Fin materialAluminium
Net weight 437 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2x180LB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
139.371 kW Fluid flow 24.19 m³/h Pressure drop 62.6 kPa
Heat rejection · Low speed (Y)
110.319 kW Fluid flow 19.14 m³/h Pressure drop 41.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 81.28 not rated not rated not rated not rated not rated
40 139.37 81.48 not rated not rated not rated not rated
45 196.01 139.12 81.65 not rated not rated not rated
50 252.16 195.35 138.90 81.81 not rated not rated
55 308.09 251.13 194.79 138.75 81.99 not rated
60 363.89 306.67 250.23 194.36 138.70 82.22

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 64.91 not rated not rated not rated not rated not rated
40 110.32 65.03 not rated not rated not rated not rated
45 154.44 110.05 65.14 not rated not rated not rated
50 198.15 153.82 109.79 65.24 not rated not rated
55 241.67 197.20 153.28 109.62 65.37 not rated
60 285.07 240.39 196.38 152.87 109.55 65.54

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 139.371 24.19 62.6
Low speed (Y) 110.319 19.14 41.3

Dimensions

Dimension drawing of BC/BD-t-2x180LB5-B01 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2500 mm
H 2400 mm
I 2260 mm
K 3050 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3050 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.