BC/BD-t-291PB5-B04 C
139.32 kW
Defrost: None
Product code: BC/BD-t-2x180LB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 42,082 m³/h |
|---|---|
| External surface | 311.2 m² |
| Inner volume | 53.4 dm³ |
| Fin material | Aluminium |
| Net weight | 437 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-2x180LB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 81.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 139.37 | 81.48 | not rated | not rated | not rated | not rated |
| 45 | 196.01 | 139.12 | 81.65 | not rated | not rated | not rated |
| 50 | 252.16 | 195.35 | 138.90 | 81.81 | not rated | not rated |
| 55 | 308.09 | 251.13 | 194.79 | 138.75 | 81.99 | not rated |
| 60 | 363.89 | 306.67 | 250.23 | 194.36 | 138.70 | 82.22 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 64.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 110.32 | 65.03 | not rated | not rated | not rated | not rated |
| 45 | 154.44 | 110.05 | 65.14 | not rated | not rated | not rated |
| 50 | 198.15 | 153.82 | 109.79 | 65.24 | not rated | not rated |
| 55 | 241.67 | 197.20 | 153.28 | 109.62 | 65.37 | not rated |
| 60 | 285.07 | 240.39 | 196.38 | 152.87 | 109.55 | 65.54 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 139.371 | 24.19 | 62.6 |
| Low speed (Y) | 110.319 | 19.14 | 41.3 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 2260 mm |
| K | 3050 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.