Product code: BC/BD-t-2x291RB1-B04 C

Heat rejection i
363.48 kW
Air flow
108,091 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 108,091 m³/h
External surface 734.8 m²
Inner volume 112.0 dm³
Fin materialAluminium
Net weight 837 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2x291RB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
363.483 kW Fluid flow 63.08 m³/h Pressure drop 91.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
288.055 kW Fluid flow 49.99 m³/h Pressure drop 60.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 211.95 not rated not rated not rated not rated not rated
40 363.48 212.50 not rated not rated not rated not rated
45 511.25 362.92 212.97 not rated not rated not rated
50 657.75 509.67 362.41 213.42 not rated not rated
55 803.62 655.14 508.28 362.09 213.93 not rated
60 949.20 800.11 652.91 507.20 362.03 214.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 169.61 not rated not rated not rated not rated not rated
40 288.06 170.04 not rated not rated not rated not rated
45 403.14 287.50 170.40 not rated not rated not rated
50 517.16 401.81 287.09 170.80 not rated not rated
55 630.66 515.05 400.72 286.87 171.25 not rated
60 743.88 627.81 513.31 399.97 286.91 171.86

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 363.483 63.08 91.4
Low speed (Y) 288.055 49.99 60.5

Dimensions

Dimension drawing of BC/BD-t-2x291RB1-B04 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2260 mm
K 5450 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.