Skip to Content

Dry cooler BC/BD-t-2x380GC5-B03 C

Dry cooler BC/BD-t-2x380GC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x380GC5-B03 C

Heat rejection i
182.49 kW
Air flow
44,262 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 3 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 03 — three-phase 400 V 50 Hz, 12-pole AC fan (in this series)

Data

Coil
Air flow 44,262 m³/h
External surface 544.7 m²
Inner volume 79.8 dm³
Fin materialAluminium
Net weight 798 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-2x380GC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
182.491 kW Fluid flow 31.65 m³/h Pressure drop 80.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
135.039 kW Fluid flow 23.42 m³/h Pressure drop 47.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.57 not rated not rated not rated not rated not rated
40 182.49 110.82 not rated not rated not rated not rated
45 252.28 182.34 111.10 not rated not rated not rated
50 321.37 251.80 182.32 111.44 not rated not rated
55 390.13 320.57 251.53 182.48 111.89 not rated
60 458.70 389.03 320.08 251.55 182.89 112.49

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 82.81 not rated not rated not rated not rated not rated
40 135.04 83.02 not rated not rated not rated not rated
45 185.57 134.95 83.25 not rated not rated not rated
50 235.57 185.26 134.98 83.55 not rated not rated
55 285.31 235.04 185.13 135.16 83.94 not rated
60 334.91 284.59 234.78 185.25 135.55 84.47

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 182.491 31.65 80.9
Low speed (Y) 135.039 23.42 47.3

Dimensions

Dimension drawing of BC/BD-t-2x380GC5-B03 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 2260 mm
K 3800 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3800 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.