BC/BD-2x680FB5-B03 C
411.73 kW
Defrost: None
Product code: BC/BD-t-2x380JC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 112,239 m³/h |
|---|---|
| External surface | 907.8 m² |
| Inner volume | 144.3 dm³ |
| Fin material | Aluminium |
| Net weight | 1,050 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.4 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2x380JC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 243.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 412.02 | 244.27 | not rated | not rated | not rated | not rated |
| 45 | 575.75 | 411.39 | 244.81 | not rated | not rated | not rated |
| 50 | 737.99 | 574.13 | 410.98 | 245.42 | not rated | not rated |
| 55 | 899.53 | 735.40 | 572.88 | 410.85 | 246.14 | not rated |
| 60 | 1060.67 | 896.00 | 733.35 | 572.14 | 411.12 | 247.09 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 190.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 318.09 | 190.51 | not rated | not rated | not rated | not rated |
| 45 | 442.13 | 317.34 | 190.79 | not rated | not rated | not rated |
| 50 | 564.88 | 440.48 | 316.76 | 191.09 | not rated | not rated |
| 55 | 687.03 | 562.39 | 439.17 | 316.45 | 191.55 | not rated |
| 60 | 808.84 | 683.72 | 560.37 | 438.29 | 316.49 | 192.23 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 412.017 | 71.50 | 78.4 |
| Low speed (Y) | 318.090 | 55.17 | 49.4 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 2260 mm |
| K | 5900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5900 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.