BC/BD-2x780AD1-B03 C
455.64 kW
Defrost: None
Product code: BC/BD-t-2x391OC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 128,113 m³/h |
|---|---|
| External surface | 857.3 m² |
| Inner volume | 123.8 dm³ |
| Fin material | Aluminium |
| Net weight | 983 kg |
| Quantity | 6 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 16,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2x391OC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 265.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 455.66 | 266.67 | not rated | not rated | not rated | not rated |
| 45 | 640.66 | 455.88 | 267.95 | not rated | not rated | not rated |
| 50 | 823.99 | 639.92 | 456.28 | 269.26 | not rated | not rated |
| 55 | 1006.44 | 822.32 | 639.55 | 456.85 | 270.64 | not rated |
| 60 | 1188.43 | 1003.90 | 821.21 | 639.67 | 457.91 | 272.23 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 455.659 | 79.09 | 78.0 |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1400 mm |
| I | 2260 mm |
| K | 4850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4850 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.