BC/BD-t-563AA5-B01 C
102.46 kW
Defrost: None
Product code: BC/BD-t-380GA5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 54,305 m³/h |
|---|---|
| External surface | 137.9 m² |
| Inner volume | 25.4 dm³ |
| Fin material | Aluminium |
| Net weight | 422 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 85.9 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-380GA5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 56.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 102.49 | 56.89 | not rated | not rated | not rated | not rated |
| 45 | 147.96 | 102.97 | 57.45 | not rated | not rated | not rated |
| 50 | 193.19 | 148.31 | 103.42 | 57.96 | not rated | not rated |
| 55 | 238.33 | 193.43 | 148.66 | 103.84 | 58.44 | not rated |
| 60 | 283.40 | 238.47 | 193.70 | 149.03 | 104.28 | 58.90 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 46.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 84.66 | 47.25 | not rated | not rated | not rated | not rated |
| 45 | 121.82 | 84.99 | 47.70 | not rated | not rated | not rated |
| 50 | 158.76 | 122.03 | 85.30 | 48.10 | not rated | not rated |
| 55 | 195.60 | 158.85 | 122.24 | 85.61 | 48.48 | not rated |
| 60 | 232.38 | 195.58 | 158.97 | 122.48 | 85.94 | 48.85 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 102.493 | 17.79 | 44.8 |
| Low speed (Y) | 84.657 | 14.69 | 31.9 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 3800 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3500 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.