BC/BD-380AC1-B03 C
95.26 kW
Defrost: None
Product code: BC/BD-t-380GC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 21,440 m³/h |
|---|---|
| External surface | 325.7 m² |
| Inner volume | 36.6 dm³ |
| Fin material | Aluminium |
| Net weight | 459 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | C |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-380GC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 58.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 95.27 | 58.71 | not rated | not rated | not rated | not rated |
| 45 | 130.71 | 95.10 | 58.81 | not rated | not rated | not rated |
| 50 | 165.76 | 130.34 | 95.02 | 58.96 | not rated | not rated |
| 55 | 200.63 | 165.21 | 130.12 | 95.06 | 59.17 | not rated |
| 60 | 235.40 | 199.91 | 164.86 | 130.07 | 95.24 | 59.48 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | 43.17 | not rated | not rated | not rated |
| 50 | not rated | not rated | 68.85 | 43.32 | not rated | not rated |
| 55 | not rated | not rated | 93.71 | 68.95 | 43.51 | not rated |
| 60 | not rated | not rated | 118.32 | 93.79 | 69.14 | 43.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 95.266 | 16.52 | 83.4 |
| Low speed (Y) | — | — | — |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 3800 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3800 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.