Skip to Content

Dry cooler BC/BD-t-380JC1-B01 C

Dry cooler BC/BD-t-380JC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-380JC1-B01 C

Heat rejection i
220.56 kW
Air flow
55,089 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 55,089 m³/h
External surface 542.8 m²
Inner volume 64.8 dm³
Fin materialAluminium
Net weight 603 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 85.7 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-380JC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
220.562 kW Fluid flow 38.25 m³/h Pressure drop 85.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
167.962 kW Fluid flow 29.13 m³/h Pressure drop 52.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 131.99 not rated not rated not rated not rated not rated
40 220.56 132.19 not rated not rated not rated not rated
45 306.48 220.06 132.35 not rated not rated not rated
50 391.51 305.37 219.68 132.60 not rated not rated
55 476.11 389.81 304.49 219.49 132.94 not rated
60 560.47 473.85 388.46 303.93 219.56 133.43

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 101.71 not rated not rated not rated not rated not rated
40 167.96 101.78 not rated not rated not rated not rated
45 231.99 167.42 101.85 not rated not rated not rated
50 295.29 230.93 166.98 101.96 not rated not rated
55 358.24 293.74 230.07 166.72 102.16 not rated
60 421.01 356.23 292.49 229.48 166.67 102.50

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 220.562 38.25 85.0
Low speed (Y) 167.962 29.13 52.4

Dimensions

Dimension drawing of BC/BD-t-380JC1-B01 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 1180 mm
K 5900 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5900 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.