BC/BD-t-363AC1-B19 C
127.04 kW
Defrost: None
Product code: BC/BD-t-480GC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 28,587 m³/h |
|---|---|
| External surface | 434.3 m² |
| Inner volume | 51.1 dm³ |
| Fin material | Aluminium |
| Net weight | 597 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-480GC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 78.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 127.00 | 78.26 | not rated | not rated | not rated | not rated |
| 45 | 174.25 | 126.78 | 78.39 | not rated | not rated | not rated |
| 50 | 220.99 | 173.77 | 126.68 | 78.59 | not rated | not rated |
| 55 | 267.49 | 220.27 | 173.48 | 126.72 | 78.87 | not rated |
| 60 | 313.85 | 266.53 | 219.80 | 173.41 | 126.97 | 79.29 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | 57.55 | not rated | not rated | not rated |
| 50 | not rated | not rated | 91.79 | 57.75 | not rated | not rated |
| 55 | not rated | not rated | 124.94 | 91.93 | 58.00 | not rated |
| 60 | not rated | not rated | 157.75 | 125.05 | 92.17 | 58.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 127.000 | 22.03 | 77.8 |
| Low speed (Y) | — | — | — |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 4850 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4850 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.