BC/BD-2x180KD5-B01 C
126.05 kW
Defrost: None
Product code: BC/BD-t-550AD5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 31,288 m³/h |
|---|---|
| External surface | 319.4 m² |
| Inner volume | 45.7 dm³ |
| Fin material | Aluminium |
| Net weight | 387 kg |
| Quantity | 5 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-550AD5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 74.66 | not rated | not rated | not rated | not rated | not rated |
| 40 | 126.17 | 74.96 | not rated | not rated | not rated | not rated |
| 45 | 175.87 | 126.00 | 75.20 | not rated | not rated | not rated |
| 50 | 224.96 | 175.32 | 125.88 | 75.47 | not rated | not rated |
| 55 | 273.76 | 224.07 | 174.91 | 125.88 | 75.79 | not rated |
| 60 | 322.41 | 272.54 | 223.37 | 174.67 | 126.01 | 76.17 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 126.167 | 21.88 | 29.1 |
| A | 4350 mm |
|---|---|
| B | 1220 mm |
| C | 930 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4100 mm |
| H | 800 mm |
| I | 880 mm |
| K | 4600 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 960 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.