Skip to Content

Dry cooler BC/BD-t-563AA1-B19 C

Dry cooler BC/BD-t-563AA1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-563AA1-B19 C

Heat rejection i
136.32 kW
Air flow
59,674 m³/h
Fans
5 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,674 m³/h
External surface 232.6 m²
Inner volume 35.4 dm³
Fin materialAluminium
Net weight 430 kg
Fans
Quantity 5
Diameter 630 mm
Speed 1,330 rpm
Power 6,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-563AA1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
136.322 kW Fluid flow 23.66 m³/h Pressure drop 16.9 kPa
Heat rejection · Low speed (Y)
118.076 kW Fluid flow 20.49 m³/h Pressure drop 13.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 72.45 not rated not rated not rated not rated not rated
40 136.32 73.62 not rated not rated not rated not rated
45 198.61 136.96 74.61 not rated not rated not rated
50 260.46 198.87 137.52 75.46 not rated not rated
55 322.10 260.37 199.10 138.04 76.24 not rated
60 383.63 321.68 260.31 199.37 138.55 76.95

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 63.02 not rated not rated not rated not rated not rated
40 118.08 64.07 not rated not rated not rated not rated
45 171.55 118.61 64.94 not rated not rated not rated
50 224.56 171.74 119.09 65.71 not rated not rated
55 277.38 224.45 171.92 119.54 66.39 not rated
60 330.07 276.97 224.37 172.15 120.00 67.04

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 136.322 23.66 16.9
Low speed (Y) 118.076 20.49 13.0

Dimensions

Dimension drawing of BC/BD-t-563AA1-B19 C
Dimension drawing
Dimensions as drawn
A 4850 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 1180 mm
K 5100 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4850 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.