BC/BD-380KB5-B01 C
149.16 kW
Defrost: None
Product code: BC/BD-t-563AB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 41,816 m³/h |
|---|---|
| External surface | 349.0 m² |
| Inner volume | 46.4 dm³ |
| Fin material | Aluminium |
| Net weight | 462 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-563AB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 87.23 | not rated | not rated | not rated | not rated | not rated |
| 40 | 149.10 | 87.52 | not rated | not rated | not rated | not rated |
| 45 | 209.25 | 148.93 | 87.77 | not rated | not rated | not rated |
| 50 | 268.85 | 208.66 | 148.79 | 88.03 | not rated | not rated |
| 55 | 328.18 | 267.87 | 208.19 | 148.72 | 88.32 | not rated |
| 60 | 387.36 | 326.83 | 267.07 | 207.88 | 148.81 | 88.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 149.103 | 25.88 | 59.0 |
| A | 4850 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 5100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4850 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.