Skip to Content

Dry cooler BC/BD-t-580GA1-B01 C

Dry cooler BC/BD-t-580GA1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-580GA1-B01 C

Heat rejection i
186.42 kW
Air flow
88,331 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 88,331 m³/h
External surface 271.4 m²
Inner volume 39.1 dm³
Fin materialAluminium
Net weight 680 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-580GA1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
186.421 kW Fluid flow 32.35 m³/h Pressure drop 33.6 kPa
Heat rejection · Low speed (Y)
152.879 kW Fluid flow 26.53 m³/h Pressure drop 23.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 100.68 not rated not rated not rated not rated not rated
40 186.42 102.10 not rated not rated not rated not rated
45 270.53 187.43 103.32 not rated not rated not rated
50 354.15 271.21 188.34 104.42 not rated not rated
55 437.54 354.56 271.88 189.21 105.46 not rated
60 520.81 437.69 355.01 272.59 190.12 106.46

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 83.15 not rated not rated not rated not rated not rated
40 152.88 84.29 not rated not rated not rated not rated
45 221.01 153.61 85.29 not rated not rated not rated
50 288.63 221.44 154.28 86.17 not rated not rated
55 356.04 288.80 221.88 154.95 87.01 not rated
60 423.32 355.96 289.03 222.37 155.66 87.81

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 186.421 32.35 33.6
Low speed (Y) 152.879 26.53 23.5

Dimensions

Dimension drawing of BC/BD-t-580GA1-B01 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1050 mm
I 1180 mm
K 5900 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5600 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.