Skip to Content

Dry cooler BC/BD-t-663AC5-B19 C

Dry cooler BC/BD-t-663AC5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-663AC5-B19 C

Heat rejection i
236.47 kW
Air flow
66,449 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 66,449 m³/h
External surface 472.9 m²
Inner volume 75.6 dm³
Fin materialAluminium
Net weight 571 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-663AC5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
236.472 kW Fluid flow 41.04 m³/h Pressure drop 92.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
196.615 kW Fluid flow 34.10 m³/h Pressure drop 66.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 139.48 not rated not rated not rated not rated not rated
40 236.47 139.72 not rated not rated not rated not rated
45 330.93 236.01 139.95 not rated not rated not rated
50 424.58 329.83 235.63 140.18 not rated not rated
55 517.86 422.88 328.93 235.37 140.49 not rated
60 610.91 515.55 421.46 328.28 235.36 140.92

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 116.91 not rated not rated not rated not rated not rated
40 196.62 117.10 not rated not rated not rated not rated
45 274.12 196.20 117.27 not rated not rated not rated
50 350.89 273.17 195.86 117.47 not rated not rated
55 427.30 349.42 272.39 195.68 117.75 not rated
60 503.52 425.33 348.22 271.86 195.70 118.11

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 236.472 41.04 92.6
Low speed (Y) 196.615 34.10 66.8

Dimensions

Dimension drawing of BC/BD-t-663AC5-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 1180 mm
K 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.