BC/BD-2X463CA1-B19 C
204.88 kW
Defrost: None
Product code: BC/BD-t-680GA5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 108,611 m³/h |
|---|---|
| External surface | 275.9 m² |
| Inner volume | 44.2 dm³ |
| Fin material | Aluminium |
| Net weight | 799 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 88.9 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-680GA5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 204.80 | 113.61 | not rated | not rated | not rated | not rated |
| 45 | 295.74 | 205.76 | 114.73 | not rated | not rated | not rated |
| 50 | 386.20 | 296.45 | 206.66 | 115.75 | not rated | not rated |
| 55 | 476.48 | 386.69 | 297.15 | 207.52 | 116.72 | not rated |
| 60 | 566.62 | 476.76 | 387.23 | 297.90 | 208.40 | 117.64 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 93.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 169.17 | 94.35 | not rated | not rated | not rated | not rated |
| 45 | 243.50 | 169.85 | 95.26 | not rated | not rated | not rated |
| 50 | 317.38 | 243.92 | 170.47 | 96.06 | not rated | not rated |
| 55 | 391.06 | 317.57 | 244.34 | 171.09 | 96.83 | not rated |
| 60 | 464.62 | 391.02 | 317.81 | 244.82 | 171.76 | 97.59 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 204.800 | 35.54 | 46.3 |
| Low speed (Y) | 169.166 | 29.36 | 32.9 |
| A | 6650 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6400 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 6950 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 6650 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.