BC/BD-763BC1-B01 C
190.46 kW
Defrost: None
Product code: BC/BD-t-680GC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 42,880 m³/h |
|---|---|
| External surface | 651.4 m² |
| Inner volume | 71.6 dm³ |
| Fin material | Aluminium |
| Net weight | 873 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-680GC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 117.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 190.47 | 117.35 | not rated | not rated | not rated | not rated |
| 45 | 261.35 | 190.14 | 117.55 | not rated | not rated | not rated |
| 50 | 331.45 | 260.63 | 189.98 | 117.85 | not rated | not rated |
| 55 | 401.20 | 330.37 | 260.18 | 190.05 | 118.28 | not rated |
| 60 | 470.75 | 399.77 | 329.66 | 260.09 | 190.42 | 118.90 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | 86.30 | not rated | not rated | not rated |
| 50 | not rated | not rated | 137.66 | 86.60 | not rated | not rated |
| 55 | not rated | not rated | 187.39 | 137.87 | 86.98 | not rated |
| 60 | not rated | not rated | 236.61 | 187.55 | 138.24 | 87.51 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 190.465 | 33.04 | 82.1 |
| Low speed (Y) | — | — | — |
| A | 6650 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6400 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 6950 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 6950 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.