BC/BD-t-2X450AB5-B09 C
165.66 kW
Defrost: None
Product code: BC/BD-t-763AA1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 62,325 m³/h |
|---|---|
| External surface | 325.7 m² |
| Inner volume | 44.2 dm³ |
| Fin material | Aluminium |
| Net weight | 586 kg |
| Quantity | 7 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 4,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-763AA1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 165.66 | 93.13 | not rated | not rated | not rated | not rated |
| 45 | 237.31 | 166.00 | 93.85 | not rated | not rated | not rated |
| 50 | 308.44 | 237.25 | 166.31 | 94.49 | not rated | not rated |
| 55 | 379.31 | 308.00 | 237.22 | 166.63 | 95.10 | not rated |
| 60 | 450.05 | 378.51 | 307.65 | 237.28 | 167.02 | 95.71 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 165.655 | 28.75 | 31.7 |
| A | 6650 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 6400 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 6900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 6650 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.