BC/BD-t-2X550AB1-B09 C
223.07 kW
Defrost: None
Product code: BC/BD-t-763AC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 55,150 m³/h |
|---|---|
| External surface | 651.4 m² |
| Inner volume | 84.4 dm³ |
| Fin material | Aluminium |
| Net weight | 678 kg |
| Quantity | 7 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 4,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-763AC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 129.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 223.04 | 130.76 | not rated | not rated | not rated | not rated |
| 45 | 312.31 | 222.89 | 131.52 | not rated | not rated | not rated |
| 50 | 400.28 | 311.40 | 222.83 | 132.20 | not rated | not rated |
| 55 | 487.63 | 398.67 | 310.69 | 222.90 | 132.93 | not rated |
| 60 | 574.65 | 485.38 | 397.40 | 310.29 | 223.21 | 133.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 223.043 | 38.68 | 16.2 |
| A | 6750 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 6400 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 7100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6750 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.