Skip to Content

Dry cooler BC/BD-t-763AD5-B19 C

Dry cooler BC/BD-t-763AD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-763AD5-B19 C

Heat rejection i
302.59 kW
Air flow
74,552 m³/h
Fans
7 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 74,552 m³/h
External surface 689.7 m²
Inner volume 99.8 dm³
Fin materialAluminium
Net weight 701 kg
Fans
Quantity 7
Diameter 630 mm
Speed 1,330 rpm
Power 8,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-763AD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
302.586 kW Fluid flow 52.48 m³/h Pressure drop 113.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
243.875 kW Fluid flow 42.29 m³/h Pressure drop 77.3 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 182.71 not rated not rated not rated not rated not rated
40 302.59 182.61 not rated not rated not rated not rated
45 419.04 301.52 182.58 not rated not rated not rated
50 534.34 417.08 300.65 182.64 not rated not rated
55 649.11 531.53 415.46 300.06 182.87 not rated
60 763.57 645.45 529.19 414.29 299.90 183.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 148.65 not rated not rated not rated not rated not rated
40 243.88 148.83 not rated not rated not rated not rated
45 336.16 243.41 149.03 not rated not rated not rated
50 427.47 335.14 243.10 149.31 not rated not rated
55 518.33 425.94 334.40 243.02 149.72 not rated
60 608.94 516.30 424.80 334.03 243.26 150.35

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 302.586 52.48 113.2
Low speed (Y) 243.875 42.29 77.3

Dimensions

Dimension drawing of BC/BD-t-763AD5-B19 C
Dimension drawing
Dimensions as drawn
A 6750 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 6400 mm
H 900 mm
I 1180 mm
K 7100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6750 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.