BE-180CB5-B01 C
82.80 kW
Defrost: None
Product code: BE-180DC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 22,173 m³/h |
|---|---|
| External surface | 358.4 m² |
| Inner volume | 50.2 dm³ |
| Fin material | Aluminium |
| Net weight | 395 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-180DC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 48.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 80.52 | 48.13 | not rated | not rated | not rated | not rated |
| 45 | 112.01 | 80.17 | 48.07 | not rated | not rated | not rated |
| 50 | 143.25 | 111.40 | 79.85 | 48.02 | not rated | not rated |
| 55 | 174.36 | 142.38 | 110.86 | 79.59 | 47.99 | not rated |
| 60 | 205.40 | 173.25 | 141.62 | 110.41 | 79.41 | 48.01 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 38.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 63.05 | 37.96 | not rated | not rated | not rated | not rated |
| 45 | 87.40 | 62.74 | 37.89 | not rated | not rated | not rated |
| 50 | 111.51 | 86.87 | 62.46 | 37.84 | not rated | not rated |
| 55 | 135.53 | 110.78 | 86.40 | 62.24 | 37.80 | not rated |
| 60 | 159.49 | 134.59 | 110.13 | 86.02 | 62.08 | 37.81 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 80.522 | 13.97 | 67.9 |
| Low speed (Y) | 63.052 | 10.93 | 44.0 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.