BE-191DD5-B04 C
109.16 kW
Defrost: None
Product code: BE-191CB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 30,071 m³/h |
|---|---|
| External surface | 564.8 m² |
| Inner volume | 67.6 dm³ |
| Fin material | Aluminium |
| Net weight | 479 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191CB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 66.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 110.78 | 66.18 | not rated | not rated | not rated | not rated |
| 45 | 154.13 | 110.24 | 66.07 | not rated | not rated | not rated |
| 50 | 197.13 | 153.24 | 109.78 | 65.97 | not rated | not rated |
| 55 | 239.96 | 195.88 | 152.45 | 109.40 | 65.92 | not rated |
| 60 | 282.70 | 238.36 | 194.78 | 151.79 | 109.12 | 65.94 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 53.23 | not rated | not rated | not rated | not rated | not rated |
| 40 | 88.17 | 53.10 | not rated | not rated | not rated | not rated |
| 45 | 122.20 | 87.70 | 52.98 | not rated | not rated | not rated |
| 50 | 155.90 | 121.40 | 87.28 | 52.86 | not rated | not rated |
| 55 | 189.47 | 154.80 | 120.70 | 86.93 | 52.81 | not rated |
| 60 | 222.95 | 188.07 | 153.84 | 120.12 | 86.68 | 52.81 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 110.775 | 19.23 | 95.7 |
| Low speed (Y) | 88.174 | 15.29 | 63.7 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.