BE-191CD5-B04 C
125.28 kW
Defrost: None
Product code: BE-191CC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,761 m³/h |
|---|---|
| External surface | 753.1 m² |
| Inner volume | 87.0 dm³ |
| Fin material | Aluminium |
| Net weight | 531 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191CC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 74.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 122.73 | 74.40 | not rated | not rated | not rated | not rated |
| 45 | 169.47 | 121.99 | 74.19 | not rated | not rated | not rated |
| 50 | 215.75 | 168.26 | 121.34 | 74.02 | not rated | not rated |
| 55 | 261.82 | 214.10 | 167.21 | 120.81 | 73.91 | not rated |
| 60 | 307.78 | 259.73 | 212.65 | 166.33 | 120.42 | 73.90 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 58.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 96.01 | 58.72 | not rated | not rated | not rated | not rated |
| 45 | 131.96 | 95.37 | 58.52 | not rated | not rated | not rated |
| 50 | 167.55 | 130.94 | 94.80 | 58.35 | not rated | not rated |
| 55 | 202.97 | 166.16 | 130.04 | 94.34 | 58.25 | not rated |
| 60 | 238.30 | 201.22 | 164.95 | 129.30 | 94.00 | 58.23 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 122.731 | 21.28 | 73.4 |
| Low speed (Y) | 96.012 | 16.65 | 47.4 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2860 mm |
| F | 1050 mm |
| G | 3460 mm |
| E1 | 2430 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3460 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.