BE-180CD5-B01 C
98.62 kW
Defrost: None
Product code: BE-191DC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 29,275 m³/h |
|---|---|
| External surface | 358.4 m² |
| Inner volume | 50.2 dm³ |
| Fin material | Aluminium |
| Net weight | 401 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191DC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 57.81 | not rated | not rated | not rated | not rated | not rated |
| 40 | 98.37 | 57.89 | not rated | not rated | not rated | not rated |
| 45 | 137.86 | 98.10 | 57.94 | not rated | not rated | not rated |
| 50 | 177.02 | 137.29 | 97.85 | 57.99 | not rated | not rated |
| 55 | 216.03 | 176.16 | 136.79 | 97.66 | 58.06 | not rated |
| 60 | 254.93 | 214.88 | 175.40 | 136.38 | 97.55 | 58.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 46.41 | not rated | not rated | not rated | not rated | not rated |
| 40 | 78.45 | 46.46 | not rated | not rated | not rated | not rated |
| 45 | 109.55 | 78.19 | 46.49 | not rated | not rated | not rated |
| 50 | 140.37 | 109.03 | 77.95 | 46.52 | not rated | not rated |
| 55 | 171.05 | 139.61 | 108.58 | 77.77 | 46.57 | not rated |
| 60 | 201.65 | 170.05 | 138.94 | 108.22 | 77.66 | 46.65 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 98.369 | 17.07 | 47.4 |
| Low speed (Y) | 78.450 | 13.62 | 31.7 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.