BE-191CC5-B04 C
115.89 kW
Defrost: None
Product code: BE-191DD1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 28,650 m³/h |
|---|---|
| External surface | 528.6 m² |
| Inner volume | 60.0 dm³ |
| Fin material | Aluminium |
| Net weight | 439 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-191DD1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 70.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 115.69 | 70.02 | not rated | not rated | not rated | not rated |
| 45 | 159.93 | 115.09 | 69.88 | not rated | not rated | not rated |
| 50 | 203.75 | 158.93 | 114.56 | 69.77 | not rated | not rated |
| 55 | 247.38 | 202.36 | 158.05 | 114.14 | 69.71 | not rated |
| 60 | 290.91 | 245.62 | 201.16 | 157.35 | 113.85 | 69.75 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 90.02 | 54.94 | not rated | not rated | not rated | not rated |
| 45 | 123.93 | 89.51 | 54.80 | not rated | not rated | not rated |
| 50 | 157.49 | 123.08 | 89.06 | 54.69 | not rated | not rated |
| 55 | 190.90 | 156.33 | 122.35 | 88.70 | 54.64 | not rated |
| 60 | 224.22 | 189.44 | 155.33 | 121.76 | 88.45 | 54.66 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 115.692 | 20.07 | 91.5 |
| Low speed (Y) | 90.024 | 15.61 | 58.6 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.