BE-280AC5-B01 C
149.84 kW
Defrost: None
Product code: BE-280BD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 41,195 m³/h |
|---|---|
| External surface | 547.5 m² |
| Inner volume | 77.4 dm³ |
| Fin material | Aluminium |
| Net weight | 596 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-280BD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 89.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 150.13 | 89.62 | not rated | not rated | not rated | not rated |
| 45 | 209.05 | 149.65 | 89.62 | not rated | not rated | not rated |
| 50 | 267.49 | 208.14 | 149.21 | 89.63 | not rated | not rated |
| 55 | 325.68 | 266.15 | 207.35 | 148.90 | 89.70 | not rated |
| 60 | 383.74 | 323.94 | 265.01 | 206.75 | 148.73 | 89.86 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 69.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 116.21 | 69.95 | not rated | not rated | not rated | not rated |
| 45 | 161.16 | 115.80 | 69.95 | not rated | not rated | not rated |
| 50 | 205.68 | 160.41 | 115.46 | 69.94 | not rated | not rated |
| 55 | 250.01 | 204.60 | 159.77 | 115.21 | 70.00 | not rated |
| 60 | 294.22 | 248.61 | 203.69 | 159.29 | 115.09 | 70.14 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 150.128 | 26.05 | 74.2 |
| Low speed (Y) | 116.208 | 20.15 | 47.1 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2660 mm |
| F | 1050 mm |
| G | 3260 mm |
| E1 | 1130 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3260 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.